Voltage Drop Calculator — pick the gauge you need

Voltage lost over a cable run, as volts and as a percentage, with a recommended gauge.

Example: Carrying 10 A over 10 m at 12 V within 3% needs AWG 7 or thicker — giving 318.5 mV of drop.

Formula

R_max = (V_supply × drop%) / I    then find the gauge that beats it

Worked example

Carrying 10 A over 10 m at 12 V within 3% needs AWG 7 or thicker — giving 318.5 mV of drop.

  1. V_allowed = V_supply × drop%

    12 V × 3%

    360 mV

  2. R_max = V_allowed / I

    360 mV / 10 A

    36 mΩ

    Across 20 m of conductor — the run doubled, because current returns.

  3. find the gauge with R/m ≤ R_max / L

    1.8 mΩ/m needed

    AWG 7 at 1.593 mΩ/m

Frequently asked questions

What wire gauge do I need for a long 12 V run?

Thicker than you expect. At 12 V a 3% drop is only 0.36 V, so a 10 A load over 10 m needs about AWG 10 in copper. The same current at 240 V would allow 7.2 V of drop and need far less copper for the same percentage.

Why does the calculation double my cable length?

Because current flows out and back. A 10 m run means 20 m of conductor in the loop, and the drop happens along all of it. Forgetting this is the most common voltage-drop mistake and makes the answer half what it should be.

Is 3% voltage drop a rule or a guideline?

A widely used design guideline, not a law of physics. Some codes recommend 3% on a branch circuit and 5% total. What matters is whether your load still works at the reduced voltage — motors and LED drivers care more than resistive heaters.

Should I size for voltage drop or for current rating?

Whichever demands more copper. Short runs are usually limited by ampacity — how much heat the wire can shed. Long runs are limited by voltage drop, often needing much thicker wire than the current alone would suggest. This tool checks both.

Related tools